Model 32S

Three Phase Duplex Alternating Pump Control with Override in Stainless Steel Enclosure

The 32S three phase duplex control panel is designed to be rugged, simple and versatile. One panel handles three voltages and covers a wide variety of pump motor amperage requirements by simply field installing overload modules - up to 32 amps each!

House in a NEMA 4X stainless steel enclosure, this industrial grade control panel is designed to alternately control two three phase pumps in industrial and commercial water and sewage systems using standard four float operation (off, lead start, lag start, high level).  Simply add the appropriate overload modules to complete your installation (sold separately).

The alternating action equalizes pump wear and this system provides time delayed override control should either pump fail.  The panel feature seal fail indicators, thermal cutout and elapsed time meters for each pump.  If a high water alarm condition occurs, the alarm switch activates the audible/visual alarm system, along with auxiliary contacts for remote alarm.  Common applications include lift stations, pump chambers and irrigation systems.

 

Model 32S

Panel Features:

  • Padlockable NEMA 4X stainless steel enclosure
  • Single-point incoming power connection
  • IEC HP rated motor starter with adjustable overload module
  • 10HP max @ 208V; 240V; 480V three phase
  • Class 10 ambient compensated overload relay
  • Pump short circuit disconnect and overload reset accessible through the inner door
  • Tri-voltage step-down control transformer
  • Separate alarm/control fuses
  • Override circuit to operate lag pump if lead float fails
  • Alternator relay for even run time
  • 22mm pilot devices with engraved labels
  • Seal leak circuits for single or double probe pumps
  • Red flashing alarm beacon and audible horn
  • Pump run indicator lights
  • Seal leak indicator lights
  • Alarm silence/test push button
  • Hand-Off-Auto selector switches
  • Overtemp shutdown for motor winding temperature switches (auto reset)
  • 16 AWG MTW control wire
  • Lag delay timing relay
  • Elapsed time meters
  • Auxiliary alarm contact

Overload Modules (sold separately, each panel requires two modules):

  • Overload module, 1.25 - 5.0 FLA
  • Overload module, 4.5 - 18.0 FLA
  • Overload module, 8.0 - 32.0 FLA

Option:

  • Lighting arrestor

UL/cUL Listed

Five-Year Limited Warranty

 

 

Model 32S

ENCLOSURE:
20 x 16 x 8 inches (50.8 x 40.6 x 20.3 cm) TYPE 4X stainless steel with mounting feet

ALARM HORN:
95 decibel rating

USA  French Canadian  Chinese